Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/18/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*1.) ALL CORRECTIONS MADE OK NOTE: BECAUSE OF EXISTING CONDITIONS AND SPACE CONSTRAINTS THE 14 3/8 FROM SIDEWALL TO CENTER IS ACCEPTED ON HANDICATPPED URINAL REMEMBER ADA REQUIRES 17" MAXIMUM AFF FOR HANIDCAPPED URINALS 2.) OK FOR C OF O PENDING ANY OTHER INSPECTIONS |
| 12/17/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.)PLUMBER PLEASE REVIEW SECTION ON CLEAN OUTS ABS SHALL NOT BE TAPPED OR THREADED. 2.) CLEAN OUTS SHALL BE READILY ACCESSIBLE NOT BURIED IN THE WALL. |
| 12/16/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) HC URINAL REQUIRES 15" FROM SIDEWALL TO CENTER. 2.) TOGGLE BOLTS HOLDING A CLEAN OUT COVER ON THE WALL DO NOT A CLEAN OUT MAKE. URINALS REQUIRE CLEAN-OUTS, CLEANOUTS IF NEEDED, TO BE EXTENDED TO THE SURFACE OF THE WALL THRU A WYE BRANCH FITTING. |
| 12/10/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) HANDICAPPED URINALS REQUIRE 15" FROM CENTERLINE TO SIDE WALL 2.) URINALS REQUIRE 6"MINIMUM FROM TOP OF URINAL TO CRITICAL LEVEL ON VACUUM BREAKER 3.) URINALS REQUIRE CLEAN OUTS. |