Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00321
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/30/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*MAIN SWITCHES INSTALLED. | |
09/26/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*CHESTNUT CONST. CALLED REQUEST TO HAVE MAC CAPISTRAN DO INSPECTION SINCE HE IS FAMILAR WITH FINAL. | |
09/24/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*CONTACTED SECRETARY AT LONG'S OFFICE #1. NO CHESTNUT PERSON ON SITE RESCHEDULE AND SET UP MEETING ON SITE. | |
09/23/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999$NO ACCESS TO POWER PANELS. ROOMS CLOSED & LOCKED PLEASE RECALL INSPECTION & ARRANGE TO LEAVE POWER ROOM UNLOCKED. | |
09/20/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NO CONTRACT ON SITE, MUST PROVIDE PLANS & ACCESS. | |
02/06/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*PANELS IN INDIVIDUAL SPACES. MUST HAVE A MAINS CIRCUIT BREAKER OR A MAIN DISCONNECTING MEANS, ALSO SINCE THEY ARE FED FROM A SERVICE ISOLATED FROMTHE BUILDING EACH SERVICE IS REQUIRED TO HAVE A CONNECTION TO THE GROUNDING ELECT GROUNDING SYSTEM. | |
02/04/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*PANELS T4,T5, & T6 MUST BE FILLED WITH 200 AMP MAIN CIRCUIT BREAKERS SEC SCHEDULE ON PLAN |