Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/23/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/22/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NEUTRAL WIRES NOT PERMITTED TO BE DOUBLED UP UNDER SINGLE LUG SCREW 2) SHEET METAL SCREWS NOT PERMITTED TO SECURE DEAD FRONT ON PANEL 3) OCCUPANCY SEPERATION DOOR MUST SELF CLOSE AND LATCH 4) INSTALL REGISTER DIFFUSERS 5) PROVIDE LADDER FOR ATTIC ACCESS 6) SECURE FLEX CONDUIT TO WALL AT A/C UNITS |