Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/24/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/17/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*ITEM #4 HAS BEEN APPROVED BY DAVE MANN ON 9-13-02. PLEASE COMPLETE ITEMS #1 & 3 OF PREVIOUS INSPECTIONS. |
| 09/06/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*WE HAVE MUTIPOLE TERMANATION UNDER LUGS AT MAIN DISCONNECT 2.) PLEASE ADDRESS MAIN DISCONNECTOR METER SCOKED 3.) NEED ACCESS TO METER SCOKET TO VERIFY BONDING 4.) MAINTAIN WORKING CLEARENCE IN FRONT OF MAIN DISCONNECT 5.) PLAN DO NOT SHOW NEW ELECTRIC SERVICE THAT WAS INSTALLED AT EXISTING LOCATION. PLEASE PROVIDE REVISED PLANS. AIR CONDITION EQUIPMENT INSTALLATION OK. |
| 04/22/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |