Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/27/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/26/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. PROPERLY RENAIL GARAGE JACK TRUSS BRACKET. 2. SHIM TRIMMERS UNDER STAIR HEADER. 3. SECURE DIRECT VENT FLUE ESCUTCHEN AND FIREPLACE TO FRAME. 4. ADD COMPLETE WIDTH CRIPPLES TO FRONT WINDOW HEADER-1ST FLOOR. 5. STRAP DOWN GAS PIPE IN 2ND FLOOR BATH CEILING AND FRONT BED CEILING. 6. REMOVE OSB SPLINTERS FROM FLUE AT ROOF. |
| 03/23/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. LEAK AT TUB DRAIN. 2. ELECT MAKE UP INCOMPLETE AT HALL BATH. FRAMING WITHHELD PENDING OTHER INTERMEDIATE. |