Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM00214
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/28/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
07/23/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | 1.) RECEPTION AREA IN RADIO | |
07/20/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) BOARD RM. CNTRL. E. 2.) OPEN OFFICE AREA CENTRAL WEST. | |
07/19/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) SOUTH 1/2 CIELING LITES OK 2.) BATHROOM APPVD | |
07/17/2001 | ELECTRIC - ABOVE CEILING | Denied | ||
07/16/2001 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*1.) MANY J BOXES UNMADE LIGHTS NOT CONNECTED CONDUIT NOT PROPERLY SUPPORTED SEE NOT BELOW. 1.) M.C. CABLE MUST BE SUPPORTED WITH 12 LINER INCHES FROM A BOX AND EVERY 6' TO 8' THERE AFTER.2.) CIELING MUST BE TIED TOP & BOTTOM. | |
07/11/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*STAIRWALL EAST. |