Permit Number - T01CM00214

Inspection Description - BUILDING ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2001 BUILDING ABOVE CEILING Approved
07/16/2001 BUILDING ABOVE CEILING Denied IVRS - Inspection 0999*1.) NO APPROVED PLANS @ SITE. 2.) I NEED 80 SEE CEILING GRID INSTALLATION GUIDE A) NO HANGERS WITHIN 8" OF END RUNS B) DEFORMED HANGERS AROUND PIPES (S.E. CORNER) C.) NO HANGER @ 4 CORNER AT LIGHT FIXUTRES D) HANGER SLOPED MORE THAN 1/6 OFF PLUMB