Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/18/2001 |
BUILDING ABOVE CEILING |
|
Approved |
|
| 07/16/2001 |
BUILDING ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*1.) NO APPROVED PLANS @ SITE. 2.) I NEED 80 SEE CEILING GRID INSTALLATION GUIDE A) NO HANGERS WITHIN 8" OF END RUNS B) DEFORMED HANGERS AROUND PIPES (S.E. CORNER) C.) NO HANGER @ 4 CORNER AT LIGHT FIXUTRES D) HANGER SLOPED MORE THAN 1/6 OFF PLUMB |