Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 09/05/2001 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*OK FOR PARTIAL CEILING TILES. INSULATE RETURN DUCTS ANGLE IRON NOT INSTALLED PROPERLY ON FIRE/SMOKE DAMPERS. INSTALL DUCT SMOKE DETECTORS. WILL CHECK ON FINAL. |
| 08/27/2001 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) OPEN UP DRYWALL TO CHECK TOP OF RATED CORRIDOR WANT SEE BACK SIDE OF COMB. DAMPERS 2.) INSULATE UNINSULATED RET.AIR SUPPLY DUCT WORK. |
| 08/24/2001 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*MECHANICAL PENETRATIONS W/COMB SMOKE FIRE DAMPERS WERE NOT INSPECTED ON 8/20/INSP. NEED TO HAVE SPACE ABOVE RATED CORRIDOR OPENED UP TO CHECK. 1.) LENGTH OF SLEEVE 2.) RETAINING AN RETAINING ANGLES MOUNT ON OUTSIDE SURFACE OF DRYWALL. |
| 08/20/2001 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*SUSPENDED/ROUGH DUCT ONLY NOTE, CONDENSATE DRAIN LINE AS DETAILED P-1 SHT. COLLECTOR LINE ON FRONT 3 UNITS NEEDS TO BE 1" HOW IS TERMINATION AT SINK TAIL PIECE GOING TO BE CONNECTED THSI APPROX 2, TONS. |