Permit: T01CM00175

Parcel: 13705505D


Addresses:

1193 W IRVINGTON RD

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
09/05/2001 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*OK FOR PARTIAL CEILING TILES. INSULATE RETURN DUCTS ANGLE IRON NOT INSTALLED PROPERLY ON FIRE/SMOKE DAMPERS. INSTALL DUCT SMOKE DETECTORS. WILL CHECK ON FINAL.
08/27/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) OPEN UP DRYWALL TO CHECK TOP OF RATED CORRIDOR WANT SEE BACK SIDE OF COMB. DAMPERS 2.) INSULATE UNINSULATED RET.AIR SUPPLY DUCT WORK.
08/24/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*MECHANICAL PENETRATIONS W/COMB SMOKE FIRE DAMPERS WERE NOT INSPECTED ON 8/20/INSP. NEED TO HAVE SPACE ABOVE RATED CORRIDOR OPENED UP TO CHECK. 1.) LENGTH OF SLEEVE 2.) RETAINING AN RETAINING ANGLES MOUNT ON OUTSIDE SURFACE OF DRYWALL.
08/20/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*SUSPENDED/ROUGH DUCT ONLY NOTE, CONDENSATE DRAIN LINE AS DETAILED P-1 SHT. COLLECTOR LINE ON FRONT 3 UNITS NEEDS TO BE 1" HOW IS TERMINATION AT SINK TAIL PIECE GOING TO BE CONNECTED THSI APPROX 2, TONS.