Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T01CM00128
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/07/2001 | MECHANICAL - INTERMEDIATE | Approved | ||
03/20/2001 | MECHANICAL - INTERMEDIATE | Partial Approval | 1) PLEASE PROVIDE STRAPS AT EACH END OF ADJ. GALVANIZED ELBOWS THEY DO NOT HAVE CAPABILITY TO STAND TENSION JOINTS POP OUT. 2) ADVISE MALL THAT FIRE DAMPER IN REAR WALL INTO COMMON CORRIDOR NEEDS TO BE ADJUSTED. RETAINING ANGLES NEED TO BE FLUSH WITH WALL SURFACE. THIS NEEDS TO BE DONE PRIOR TO FINAL. I RELIZE THIS IS NOT INVOLVED WITH TI AS NOTED ON APPROVED PLAN |