Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM00125
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
| 01/31/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* NOTES 2X4 LAYIN FLOURESCENT FIXTURES NEED TO BE SECURED TO CEILING GRID #8 SCREWES SUPPORT MC AND FLEX WITHIN 12" EACH BOX AND AT 6' INTERVALS, DO NOT USE GRID WIRES 334-10 NEC 350-18NEC PROPERLY TERMINATE MC CABLES WITH LISTED CONNECTORS SUPPORT TRACK LIGHTING INDEPENDENT OF GRID SYSTEM 300-11 NEC |