Permit: T01CM00125

Parcel: 11205283F


Addresses:

2954 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM00125

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/02/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
01/31/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*
NOTES 2X4 LAYIN FLOURESCENT FIXTURES NEED TO BE SECURED TO CEILING GRID #8 SCREWES
SUPPORT MC AND FLEX WITHIN 12"
EACH BOX AND AT 6' INTERVALS, DO NOT USE GRID WIRES 334-10 NEC
350-18NEC
PROPERLY TERMINATE MC CABLES WITH LISTED CONNECTORS
SUPPORT TRACK LIGHTING INDEPENDENT OF GRID SYSTEM 300-11 NEC