Permit: T01CM00116

Parcel: 10714376C


Addresses:

555 E GRANT RD


Inspection Status: Partial Approval

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T01CM00116

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Partial Approval

Date Description Inspector Results Comments
04/03/2001 PLUMBING - GAS PRESSURE TEST Partial Approval GAS PIPING FROM METER TO REGULATOR TEST OK. PLEASE COMPLETE VENT AND GAS PIPING TO UNIT. PROVIDE TEST AND CALL FOR FINAL
04/02/2001 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999* 1) MUST PROVIDE AIR PRESSURE TEST OF 60LBS MINIMUM FOR 30 MINUTES SEE SEC 1204.3.2 94 UPC 2) MUST PROVIDE LISTING ON GAS SHUT OFF VALVE AT REGULATOR
3) REGULATOR MUST BE TAGGED AND SECURED NON REMOVABLE AND STATE WHAT CALLS ON SEC.1218.4 SUB NOTE #4 94 UPC 4) PROVIDE LISTING FOR REGULATOR FOR POSITION OF VENT
03/30/2001 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection 0000* 1) CONTRACTOR NOT ON JOB
AT THIS TIME. 2) PLEASE PROVIDE APPROVED PLAN ON JOB WITH TOTAL LENGTH AND TOTAL BTU'S AT TIME OF NEXT INSP.