Permit: T01CM00111

Parcel: 137338950


Addresses:

6285 S BEARDSLEE DR

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
02/22/2001 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
02/15/2001 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/1. PROVIDE COT APPROVED TRUSS CALC'S PROVIDE FRAMING PLAN. 2. PROVIDE OSB AT FRONT COLUMN. 3. SECURE ALL ANCHOR BOLTS. 4. PROVIDE H2.5 AT GIRDER TRUSS FRONT BEDROOM. 5. PROVIDE 1/8 INCH GAP AT OSB SHEARWALL EDGES AS PER MANF. SPECS. 6. POST TENSION CABLES NOT PULLED NOT OK TO LOAD ROOF. 7. TRENCH FOR CABLE DROP NOT DUG OUT.