Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00103
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/11/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
05/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) BOND CONDUIT BOTH ENDS WITH GROUNDING ELECTRODE CONDUCTOR 2) DOUBLE LUGGING AT GROUNDS 3) CANNOT BEND GROUND RODS 4) NEED BONDING DEVICES BEFORE 1ST DISCONNECTING MEANS AT SERVICE 250-94 5) CLEAN SURFACE UNDER GROUND BAR |
|
05/04/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) NEED BONDING DEVICE BOTH END OF CONDUIT WITH GROUNDING ELECTRODE CONDUCTOR 2) CONDUIT TO MEET DEPTH REQUIREMENTS 300-5 3) BOND GUTTER ENCLOSRE 250-96 4) NEED BONDING DEVICES ON CONDUIT BEFORE 1ST DISCONNECTING MEANS AT SERVICE 250-94 5) NEED REJECTION PINS 6) SECURE SEAL TITE AS PER CODE 7) LABEL DISCONNECT 8) CLEAN SURFACE UNDERGROUND BAR 250-12 9) SECURLEY MOUNT DISCONNECT |