Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM00103

Parcel: 11702144A


Addresses:

1015 N STONE AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM00103

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/11/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
05/10/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) BOND CONDUIT BOTH ENDS WITH GROUNDING ELECTRODE CONDUCTOR
2) DOUBLE LUGGING AT GROUNDS 3) CANNOT BEND GROUND RODS 4) NEED BONDING DEVICES BEFORE 1ST DISCONNECTING MEANS AT SERVICE 250-94
5) CLEAN SURFACE UNDER GROUND BAR
05/04/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) NEED BONDING DEVICE BOTH END OF CONDUIT WITH GROUNDING ELECTRODE CONDUCTOR 2) CONDUIT TO MEET DEPTH REQUIREMENTS 300-5 3) BOND GUTTER ENCLOSRE 250-96 4) NEED BONDING DEVICES ON CONDUIT BEFORE 1ST DISCONNECTING MEANS AT SERVICE 250-94 5) NEED REJECTION PINS 6) SECURE SEAL TITE AS PER CODE 7) LABEL DISCONNECT
8) CLEAN SURFACE UNDERGROUND BAR 250-12
9) SECURLEY MOUNT DISCONNECT