Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 04/30/2001 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 04/27/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999* |
| 04/17/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999* |
| 04/13/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*/UFER GROUND NOT INSTALLED OR LOCATED. INSTALL 2 GROUND RODS 8 FT LONG AT LEAST 6 FEET APPART CONNECTED TO SERVICE PANEL WITH CONTINOUS CONDUCTOR SEE 1/25 PLAN CALLS FOR UNDERGROUND SRVC |