Permit: T01CM00058

Parcel: 133398850

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM00058

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
05/30/2001 FRAMING Approved IVRS - Inspection 0000*
05/23/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) NEED PROPER CLEARANCE AT FIREPLACE FLUE AT ROOF SHEATHING 2) TEMP GLASS AT 3 OPENINGS 3) A.B. AT BATH WEST WALL
05/17/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) WESTSIDE PROPERTY LINE, QUESTION DETAIL, CLOSER THAN 3' TO PROPERTY LINE, ASK REGULAR INSPECTOR, WAS HERE WHEN HOUSE WAS STARTED, MORE FAMILAR WITH THE SITUATION 2) FIREPLACE FLUE TO CLOSE TO COMBUSTIBLE FLUE STRAPS NOT ATTACHED, COMBUSTIBLE MATERIAL BELOW HEARTH NEEDS SAFETY STRIP 3) BELOW RANGE DUCT STUD CUT NOT SECURED 4) FLOOR CUT KITCHEN WIRE TO BE IN CONDUIT WITH CORRECT COVER 5) BEAM REAR BATH NOT SECURED AT ENDS 6) FINISH REMOVING WOOD FORM AT REAR SHOWER 7) PEX LINE TO CLOSE TO LIGHT CAN, REAR BATH, REAR CLOSET AND HALLWAY 8) CENTER BATH LAUNDRY TRAY 3/4" WATER LINE OUT OF WALL 9) ANCHOR BOLT WEST WALL LAUNDRY 10) FRONT BEDROOM CLOSET CAN LITE/PEX 12" 11) SAFETY GLASS, FRONT, DOOR AND FIXED PANELS EASTSIDE WALL