Inspection History: PLUMBING - FINAL
Permit Number - T01CM00042
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/17/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*1)PLUMBING FINAL OK.2)DISHWASHER DRAIN INTO GREASE TRAP HAS BEEN ALLOWED AS PER DAVE MANN AND STEVE LONG WITH FLOW CONTROL INSTALLED IN LINE.3)OK FOR C OF O. | |
05/09/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1) BACKFLOW PREVENTOR FOR TEA DISPENSOR OK 2) FLOW CONTROL FOR TRI- COMPT SINK OK 3) ANSUL VALVE SIGN ON WALL OK 4) FINAL INSP. WILL BE APPROVED UPON DECISION FROM CODES ADMINSTRATOR ON DISHWASHER BEING DISCHARGED INTO GREASE TRAP | |
05/08/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1) TRIPLE COMPARTMENT SINK REQUIRES A FLOW CONTROL RATED FOR GREASE TRAP (PROVIDE LISTING ON FLOW RATING) SEE SEC. 1011.3 94 UPC 2) PROVIDE LISTING FOR REGULATORS AT GAS APPLIANCE IF REGULATORS WERE NOT PROVIDED BY APPLIANCE MANUFACTURER 3) COFFEE, ICE TEA MACHINE REQUIRES A BACKFLOW PREVENTER AT WATER SUPPLY 4) MUST PAINT ON WALL OR CEILING ANSUL LOCATION 5) DISHWASHING MACHINE CAN NOT DISCHARGE INTO GREASE TRAP. SEE SEC. 1013.0 94 UPC REFER BACK TO PLAN CHECKER ALSO REFER TO TABLE 10-2 94 UPC |