Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1) WASTE AND VENT SYSTEM OK 2) OVER HEAD WATER DISTRUBUTION OK 3) OK TO DRYWALL UPON BLDG INSP. APPROVAL | |
| 03/13/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) 2" HORIZONTAL WASTE LINE HAS OVER LOAD ON FIXTURE UNITS. 2" CAN ONLY HAVE 8 FIXTURE UNITS ON HORIZONTAL. 2) SOIL WATER TEST OK |
|
| 03/09/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) CAN NOT HAVE A WASTE LINE CONNECT CONVENTIONALLY TO THE VENT OF THE WATER CLOSET. 2) MUST PROVIDE TRAP PRIMETER FOR FLOOR DRAIN AS PER PLAN 3) MUST PROVIDE C.O. FOR FLOOR SINK AT PREP SINK 4) MUST HAVE AREA OF VENTS TO MATCH SIZE OF BLDG DRAIN TRUNK LINE 5) MUST PROVIDE WATER TEST ON WASTE AND VENT SYSTEM 6) MUST HAVE REVISED AND APPROVED DRAWINGS BEFORE NEXT INSP. |