Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00034
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
10/15/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) USE APPROVED CONNECTORS FOR M/C CABLE TO BOX CONNECTIONS 2.) GROUND METAL BOX 3.) CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR PUMPS, COMPRESSOR, WATER HEATER 4.) CORRECTLY WIRE VACCUM DISCONNECT FOR OVERCURRENT PROTECTION 5.) PLEASE PROVIDE PAPER WORK FOR LABELING OF VACCUM PUMP. | |
10/02/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) LABEL PANEL ON OUTSIDE OF COVER 2.) FINISH INSTALLATION OF DEVICES 3.) HOOK UP WATER HEATER 4.) FINISH INSTALLATION OF X-RAY EQUIPT 5.) BOND METER ENCLOUSER AND GUTTERS 6.) LABEL DISCONNECTS AND METERS CORRECTLY 7.) FINISHED CIRCLED ITEMS. | |
09/11/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) NEED OUTSIDE LIGHTS INSTALLED 2.) FINISH STORAGE ROOM 3.) DENTAL EQUIPMENT TO BE INSTALL AND CHAIRS TO HAVE LISTING AND LABELED. 4.) ISOLATE ISOLATED GROUND AND IDENTIY WITH TRAILER 5.) INSTALL CONDUCTORS IN A CLOCKWISE DIRECTION UNDER SCREW RECEPTACLES 6.) FINISH ALL ELECTRICAL CONNECTIONS. 7.) WORKING CLEARANCE IN FRONT OF SERVICE REGISTRATION. |