Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/07/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/05/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/REINSPECTION FEE REQUIRED PRIOR TO NEXT INSPECTION. 1. HOUSE INSULATED AND STOCKED CANNOT VARIFY PREVIOUS INSPECTION REQUIREMENTS SEVERAL ITEMS STILL NOT REPAIRED OR COMPLIED WITH. 2. REMOVE INSULATION FROM WALLS STOCK ALL DRYWALL FLAT. |
| 03/01/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. 7 PSI AT GAS LINE PROVIDE MINIMUM OF 10 PSI 2. OVER KNOTCHED DBL TOP PLATE AT DRYER VENT PROVIDE ENGINEER'S FIX. 3. BLOCK UNDER ROOF NEAR DRYER VENT. 4. SEAL WEATHER BARRIER INSIDE WHERE TORN. 5. ROOF NOT DRIED IN CAN'T VARIFY CLEARANCE FROM FLUE PIPE VENT. 6. PROTECT PRESSURE RELIEF LINE AT HOT WATER GARAGE SIDE. 7. RETURN AIR DUCT NOT SIZED AS PER PLAN REVISE PLAN FOR AS BUILT OF BUILD PER PLAN. 8. PROVIDE TEST TO ABS WASHER DRAIN WAS RELOCATED AND IS DIRECT CONTACT WITH CONCRETE. |