Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 03/20/2001 | ELECTRIC - FINAL | Not ready for Inspection | 1) NEED TO LIST MACHINERY ON ENGINEERS APPROVAL 2) BOND DISCONNECT WITH BOND SCREW 3) RECALL | |
| 03/14/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* 1) ALL EQUIPMENT MUST BE LISTED AND PROPER DATA TAGS AFFIXED THERE TO. 2) LABEL DISCONNECT AND PANEL BOARD. 3) BOND EACH DISCONNECT WITH BOND SCREW 4) BOND JUMPER ON SUPPLY SIDE MUST BE 1/0 CU. MIN. 5) NEW PANEL BE NOT RAIN TIGHT 6) NEED GFI PROTECTED RECEPTICLE FOR SHOP |