Permit: T01CM00003


Addresses:

908 N ALAMO AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/13/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL S.T.O.I.
01/07/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) UNCOVER COUNTER POISE GROUNDING AND GROUNDRODS AS PER PREVIOUS INSPECTION.
2.) CANNOT STACK LUG DUE TO SURFACE CONTACT
3.) A MAIN BONDING JUMPER SIZED PER 250-66 IS NEEDED.
4.) PLEASE LABEL ON OUTSIDE OF COVER MINI POWER ZONE, DISCONNECT
5.) PLEASE PROVIDE A LETTER VERIFYING TORQUEING OF SERVICE SECTIONS
6.) COPPER BARE CONDUCTOR TO BE DIRECT BURRIED. PLEASE PROVIDE LETTER FOR INSTALLATION IN CONDUIT.
7.) PLEASE PROVIDE A LETTER FOR DELETED ELECTRIC FROM PLANS.