Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM00002
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/13/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
01/07/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) INSTALL PANEL DIRECTORY OR LABEL BREAKERS 2.) TIGHTEN LOOSE SEAL TITE FITTINGS 3.) TIGHTEN LOOSE TERMANAL CONNECTIONS 4.) CAN NOT STACK LUGS DUE TO SURFACE CONTACT. OK INJECTION WALLS. |