Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T01BU03380

Parcel: 110045570

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/18/2001 FRAMING Approved
12/14/2001 FRAMING Denied IVRS - Inspection 0999*NOT APPROVED/ ADD H2.5 TO RAFTERS AT BEAM SECURE TOP OF BEAM TO COLUMN.