Permit: T01BU03331

Parcel: 116271920

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/11/2001 FRAMING Approved IVRS - Inspection 0000*PER APPROVED REVISION BY RGA. 1.) APPROVED REVISION ALLOWS FOR 1/2" LAG BOLTS 16" O.C. THROUGH 1" FOAM WITH 1/2" STUCCO THERE IS NO WOOD TO WOOD BEARING FROM LEDGERS TO EXISTING STRUCTURE.
12/07/2001 FRAMING Denied IVRS - Inspection 0999*1.) YOUR LEDGER IS 8" WIDE NOT 5 1/2"; NOT 3" AND NOT 2 1/2" WHICH IS WHAT YOU'VE SHOVED BEHIND THE ROUGH SAWN. (NOT COUNTING) THE LEDGER OVER THE DOOR AND THE END PIECES WHERE YOU'VE PUT NOTHING.2.) A RE-INSPECTION FEE IS NOW NECESSARY YOU MAY PAY IT @ 201 N. STONE. 3.) STAMPED/APPROVED "FIX IS ALSO REQUIRED..
12/06/2001 FRAMING Denied IVRS - Inspection 0999*1.) LEDGERS NOT PROPERLY CUT IN AND ATTACHED TO EXISTING BUILDING. 2.) SIMPSON BEAM SEATS NOT INSTALLED. 3.) ALL FRAMING TO BEAR WOOD TO WOOD (SEE CORRECTION #1 ABOVE). 4.) 3 EACH GALVANIZED 16D REQUIRED TO FACE NAIL HIP RAFTERS.