Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/11/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000*PER APPROVED REVISION BY RGA. 1.) APPROVED REVISION ALLOWS FOR 1/2" LAG BOLTS 16" O.C. THROUGH 1" FOAM WITH 1/2" STUCCO THERE IS NO WOOD TO WOOD BEARING FROM LEDGERS TO EXISTING STRUCTURE. |
| 12/07/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*1.) YOUR LEDGER IS 8" WIDE NOT 5 1/2"; NOT 3" AND NOT 2 1/2" WHICH IS WHAT YOU'VE SHOVED BEHIND THE ROUGH SAWN. (NOT COUNTING) THE LEDGER OVER THE DOOR AND THE END PIECES WHERE YOU'VE PUT NOTHING.2.) A RE-INSPECTION FEE IS NOW NECESSARY YOU MAY PAY IT @ 201 N. STONE. 3.) STAMPED/APPROVED "FIX IS ALSO REQUIRED.. |