Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/11/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000*PER APPROVED REVISION BY RGA. 1.) APPROVED REVISION ALLOWS FOR 1/2" LAG BOLTS 16" O.C. THROUGH 1" FOAM WITH 1/2" STUCCO THERE IS NO WOOD TO WOOD BEARING FROM LEDGERS TO EXISTING STRUCTURE. |
| 12/07/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*1.) YOUR LEDGER IS 8" WIDE NOT 5 1/2"; NOT 3" AND NOT 2 1/2" WHICH IS WHAT YOU'VE SHOVED BEHIND THE ROUGH SAWN. (NOT COUNTING) THE LEDGER OVER THE DOOR AND THE END PIECES WHERE YOU'VE PUT NOTHING.2.) A RE-INSPECTION FEE IS NOW NECESSARY YOU MAY PAY IT @ 201 N. STONE. 3.) STAMPED/APPROVED "FIX IS ALSO REQUIRED.. |
| 12/06/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*1.) LEDGERS NOT PROPERLY CUT IN AND ATTACHED TO EXISTING BUILDING. 2.) SIMPSON BEAM SEATS NOT INSTALLED. 3.) ALL FRAMING TO BEAR WOOD TO WOOD (SEE CORRECTION #1 ABOVE). 4.) 3 EACH GALVANIZED 16D REQUIRED TO FACE NAIL HIP RAFTERS. |