Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 12/12/2001 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000*1) MAKE SURE YOU LIFT REBAR 3" OFF BOTTOM OF TRENCH WHEN YOU POOR CONCRETE. 2.) LAY BLOCK TO 6' TALL THEN CALL FOR PREGROUT INSPECTION. |
| 12/10/2001 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Cancelled |
IVRS - Ri canceled |
| 12/07/2001 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999* |
| 12/03/2001 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*1.) USE #4 REBAR FOR HORIZONTAL 2.) FOOTER TO BE 20" WIDE & 12"DEEP 3.) PROVIDE VERTICAL REINFORCEMENT EVERY 48" MIN 20" ABOVE FOOTER. |