Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T01BU02775
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2002 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection 0000* | |
| 04/24/2002 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection 0245*NOTES 1.) INSTALL BOND BUSHING ON CONDUITS USING REDUCING WASHERS AT 10X10 J-BOX 2.) SEAL KO'S IN J-BOX CONDUIT TERMINATIONS KO'S ARE SLIGHTLY OVERSIZED LEAVING GAPS AT CONNECTORS. 3.) BOND GAS PIPING IN POLE EQUIPMENT YARD 4.) SUPPORT 1/2" CONDUIT BELOW J-BOX. AND TIME CLOCK PANEL. | |
| 04/22/2002 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection 0999*ELECT NOT AT POOL COULD NOT LOCATE ALL POOL AREA CLOSED OFF BY PATIO POOLS. FOUND SUPERIN TENDENT HE TIED TO CALL ELECTRICIANS NO ANSWER WILL CALL FOR TUE INSP. | |
| 03/21/2002 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection 0000*OR BONDING ANCHORS. | |
| 03/20/2002 | POOL/SPA ELECTRIC | Not ready for Inspection | IVRS - Inspection 0000* | |
| 12/13/2001 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection 0000*OK UNDERGROUND/ OK GROUNDING SYSTEM (UFERS.) |