Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
| Date |
Description |
Inspector |
Results |
Comments |
| 07/16/2002 |
POOL/SPA ELECTRIC |
|
Approved |
IVRS - Inspection 0000*OK FINAL |
| 07/12/2002 |
POOL/SPA ELECTRIC |
|
Partial Approval |
IVRS - Inspection 0000* |
| 06/11/2002 |
POOL/SPA ELECTRIC |
|
Denied |
IVRS - Inspection 0999*RICK GO TO OFFICE FOR ACCESS TO POOL. 1.) PLEASE PROVIDE HOLD DOWN DEVICE FOR MAIN BREAKER 384-16(G) 2.) WE STILL NEED TO SUPPORT JUNCTION BOX BY FENCE. 3.) PANEL COVER IS NOT LABELED AS REQUESTED #3 PREVIOUS INSPECTIONS 110-22. 4.) NO ELECTRICAL PLANS ON SITE. NEED PLANS AND ACCESS TO WHERE THE FEED FOR THIS SERVICE ORIGINATES FROM. WAITED 20 MIN. FOR CONTRACTOR NO ONE SHOWED UP LEFT PAPER WORK IN OFFICE SANDY. |
| 06/07/2002 |
POOL/SPA ELECTRIC |
|
Denied |
IVRS - Inspection 0935*GATES LOCKED NO ACCESS A REFEE HAS BEEN ASSESSED. |
| 06/03/2002 |
POOL/SPA ELECTRIC |
|
Denied |
IVRS - Inspection 0920*LOCKED NO ACCESS. |
| 05/28/2002 |
POOL/SPA ELECTRIC |
|
Not ready for Inspection |
IVRS - Inspection 0000*CANCELED BY BRAIN. |
| 05/23/2002 |
POOL/SPA ELECTRIC |
|
Denied |
IVRS - Inspection 0245*NOTES SPOKE TO POOL CONTR, WILL RE-CALL. FOR INSPECION TUES, 28TH TO SET UP MEETING WITH INSPECTOR. |
| 05/15/2002 |
POOL/SPA ELECTRIC |
|
Denied |
IVRS - Inspection 0999* NO WORK PROGRESS PLEASE COMPLETE PREVIOUS INSPECTION REQUEST A REFEE MAY BE ACCESSED IF ITEM ARE NOT CORRECTED NOTE: POOL IS IN USE WITHOUT FINAL INSPECTION OR C OF O. |
| 03/14/2002 |
POOL/SPA ELECTRIC |
|
Partial Approval |
IVRS - Inspection 0000*1.) WE NEED TO SUPPORT THE JUNCTION BOX NEXT TO FENCE 2. PLEASE PROVIDE A MAIN BREAKER FOR POOL PANEL AS PER CODE 225. 3.) PLEASE LABEL PANEL COVER. 4.) WHERE ARE PLANS AND ACCESS TO PANEL THAT IS FEEDING POOL PANEL? |
| 10/03/2001 |
POOL/SPA ELECTRIC |
|
Partial Approval |
IVRS - Inspection 0000*OK TO GUNITE. |
| 10/02/2001 |
POOL/SPA ELECTRIC |
|
Denied |
IVRS - Inspection 0999*1.) FIXTURE HOUSING TO HAVE NATIONALY RECONIZGED TESTING LABITORY (NRTL) LABEL AND LISTING AS PER CODE 110-3. INSTRUCTIONS PAPERWORK AND FIXTURE HOUSING DO NOT REFLECT THESE LABEL OR LISTING. |
| 09/30/2001 |
POOL/SPA ELECTRIC |
|
Denied |
IVRS - Inspection 0999*1.) PLEASE PROVIDE MANUFACTURS LISTING AND LABELING OF WET A FIXTURES. 2.) NO MORE THAN 360 ALLOWED IN CONDUIT RUNS. |