Inspection Status: Approved
Inspection History: STEM WALL/RETAINING WALL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/01/2001 |
STEM WALL/RETAINING WALL |
|
Approved |
|
| 07/20/2001 |
STEM WALL/RETAINING WALL |
|
Not ready for Inspection |
IVRS - Inspection 0000*EXC./L.O. APPROVED FOR 6" OR 8" CMV. |
| 07/19/2001 |
STEM WALL/RETAINING WALL |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) THE FOOTING DESIGN ON THE JOB IS FOR A 6" OR 8" CMV WALL. THE JOB IS STOCKED WITH 4" CMU. 2.) THE FOOTING DESIGN ON THE JOBS REQUIRES 20" WIDTH WHICH IS MEASURED AT THE BOTTOM OF THE FOOTING THE FOOTING, AS DUG, IS LESS THAN 20" WIDE. EITHER: CHANGE THE BLOCK ON THE JOB TO 6" OR 8" AND WIDEN THE FOOTING TO 20" AND HAVE REINSPECTED. OR HAVE A 4" FOOTING DESIGN APPROVED BY MR ARAVYO, CITY PLAN CHECKER, AND BRING A COPY TO THE JOB FOR REINSPECTION. |