Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: POOL/SPA PRE-GUNITE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2002 |
POOL/SPA PRE-GUNITE |
|
Approved |
IVRS - Inspection 0000* |
| 07/10/2001 |
POOL/SPA PRE-GUNITE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) POOL ONLY-SPA NOT READY GAS LINE AND ELECTRIC SERVICE RUN NOT IN 2) OK-TO GUNITE POOL ONLY |