Inspection Status: Approved
Inspection History: MODULAR - ELECTRIC INSPECTION
| Date |
Description |
Inspector |
Results |
Comments |
| 05/09/2001 |
MODULAR - ELECTRIC INSPECTION |
|
Approved |
IVRS - Inspection 0000* |
| 05/08/2001 |
MODULAR - ELECTRIC INSPECTION |
|
Denied |
IVRS - Inspection 0999* 1) GROUNDING ELECTRODE NOT DRIVEN INTO EARTH NOR IS 8' OF LENGTH 30" DEEP. 2) SERVICE RISER NOT BONDED TO GROUNDING ELECTRODES 3) LIQUID TIGHT CONDUIT MAY NOT BE HANGING SUCH THAT IT PROVIDES A TRIP HAZARD OR COULD BE UNINTENTIONALLY PULLED OUT OF PANELS |
| 05/07/2001 |
MODULAR - ELECTRIC INSPECTION |
|
Not ready for Inspection |
IVRS - Inspection 0000* |