Permit: T01BU01197

Parcel: 133372030

Inspection Status: Approved

Inspection History: MODULAR - ELECTRIC INSPECTION

Permit Number - T01BU01197

Inspection Description - MODULAR - ELECTRIC INSPECTION

Inspection Status - Approved

Date Description Inspector Results Comments
05/09/2001 MODULAR - ELECTRIC INSPECTION Approved IVRS - Inspection 0000*
05/08/2001 MODULAR - ELECTRIC INSPECTION Denied IVRS - Inspection 0999* 1) GROUNDING ELECTRODE NOT DRIVEN INTO EARTH NOR IS 8' OF LENGTH 30" DEEP. 2) SERVICE RISER NOT BONDED TO GROUNDING ELECTRODES 3) LIQUID TIGHT CONDUIT MAY NOT BE HANGING SUCH THAT IT PROVIDES A TRIP HAZARD OR COULD BE UNINTENTIONALLY PULLED OUT OF PANELS
05/07/2001 MODULAR - ELECTRIC INSPECTION Not ready for Inspection IVRS - Inspection 0000*