Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA PRE-GUNITE
Permit Number - T01BU01014
Inspection Description - POOL/SPA PRE-GUNITE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2001 | POOL/SPA PRE-GUNITE | Approved | IVRS - Inspection 0000* | |
04/23/2001 | POOL/SPA PRE-GUNITE | Denied | IVRS - Inspection 0999*/1) PLAN CALLS FOR #3 BARS VERTICAL AT 9" CENTERS UP TO 36" OVER 36" #3 AT 3" CENTERS 2) HORIZONTALS #3 AT 6" CENTERS EXTEND VERTICAL REBAR MIN 2' POST END OF RADIUS AT BOTHAR ? 3) POOL CONTRACTOR TO SUPPLY ASBUILT ENG'R | |
04/18/2001 | POOL/SPA PRE-GUNITE | Not ready for Inspection | IVRS - Inspection 0000*/1) PLUMBING LEAKING 2) STEEL NOT PER PLAN |