Permit: T01BU00844

Parcel: 123052220


Addresses:

2201 N TUCSON BL

Inspection Status: Approved

Inspection History: POOL/SPA FINAL/BARRIER

Date Description Inspector Results Comments
06/20/2001 POOL/SPA FINAL/BARRIER Approved IVRS - Inspection 0000*
06/14/2001 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection 0999*/ 1) 22 VOLT NON METALIC CONDUIT MUST BE A MINIMUM OF 18" BELOW GRADE NFC TABLE 300-5 2) PROPER COLOR CODE OF 220V CIRCUIT CONDUCTORS NOT MAINTAINED 3) LABEL ALL CIRCUITS IN ELECTRIC SUB PANEL 4) ELECTRIC SUB PANEL MUST HAVE AN ISOLATED NEUTRAL BAR 5) 20 AMP BREAKER CANNOT BE DOUBLE LUGGED OR HAVE 14 GUAGE WIRE 6) FILL ALL OPEN KNOCKOUTS IN SUB PANEL 7) CALLED OFFICE OF ROBERT EAST, NOT IN
06/11/2001 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection 0999*/ 1) A GFCI PROTECTED OUTLET REQUIRED BETWEEN 10 AND 20 FEET OF POOL, NONE INSTALLED 2) MANY VERTICAL MEMBERS OF POOL BARRIER HAVE GAPS LARGER THAN 4"-NO AREA OF POOL BARRIER CAN PERMIT A 4" BALL TO PASS THRU 3) UNDERGROUND ELECTRIC CONDUIT FROM POOL EQUIPMENT TO ELECTRIC SERVICE WAS NOT INSPECTED-EXPOSE 4) ELECTRIC WEATHER TIGHT CONNECTIONS LOOSE 5) INSTALL BACK UP WASHERS AT ALL EXCENTRIC KNOCK OUTS