Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
03/15/2001 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000* MAJOR ELEC. IS CONTRACTOR OK TO CLEAR TEMP SERVICE
03/13/2001 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999* 1) GROUND ROD TO BE DRIVEN 2) WIRE TO BE LISTED FOR DIRECT BURIAL
3) NEED METAL ADDRESS LABELS 4) LABEL BREAKERS 5) USE ONLY BREAKERS APPROVED AND LISTED FOR PANEL 6) CONDUIT OVER FILLED FOR CONDUCTORS 7) USE APPROVED FITTINGS TO GFI BOX 8) TIGHTEN ALL LOOSE FITTINGS 9) USE CORRECT SIZED GROUNDING CONDUCTOR
10) PANEL MISSING DEAD FRONT 11) VERIFY ELECTRICAL CONTRACTOR
03/12/2001 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*1) NEED SOILD POLE TO SUPPORT PANEL 2) NEED RISER INSTALLED 3) NEED GROUNDING ELECTRODE SYSTEM 4) FINISH SET UP