Inspection History Details
Inspection Status: Violation
Inspection History: FOLLOW UP CODE VIOLATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2001 | FOLLOW UP CODE VIOLATION | Violation | SENT OUT NOV 3-29-01 | |
| 02/06/2001 | FOLLOW UP CODE VIOLATION | Correction Required | 1) OUTLETS NEED TO BE INSTALLED FOR SPACING AS PER CODE 210-52 2) NEED 2 CIRCUTS IN KITCHEN TO SERVE COUNTER TOPS 3) NEED LIGHT FIXTURE AT ENTRANCE DOOR 4) NEED LIGHTING AT STAIRS 5) FIXTURE WIRES SPLICED IN CORD 6) NEED LISTED AND LABELED LIGHT FIXTURES FOR DISPLAY SHELVES 7) EXPOSED CONDUCTORS ON DISPLAY SHELVES 8) CORD PASSING THROUGH DRYWALL 400-7 9) SUPPORT CONDUIT AS PER CODE |
|
| 02/06/2001 | FOLLOW UP CODE VIOLATION | Denied | NO MECH INSTALLED YET(A/C,HEATING,RETURN DUCT SYSTEMS, VENTILATION) | |
| 04/14/2000 | FOLLOW UP CODE VIOLATION | Violation | VIOLATION | |
| 02/14/2000 | FOLLOW UP CODE VIOLATION | Violation | VIOLATION |