Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T00PL02551
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
03/15/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1) 3/4" GAS LINE IS TOO SMALL OF LINE FOR TOTAL CFH DEMAND. THIS LINE MUST BE 1" UP TO FIRST APPLIANCE FROM METER SEE TABLE 12-3 94 UPC | |
01/03/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* MUST HAVE ACCESS TO ALL GAS APPLIANCS INSIDE DWELLING PLEASE CALL 791-5550 TO MAKE A APPOINTMENT. GAS PRESSURE TEST WAS DOWN TO ZERO LBS MUST HAVE 10 LBS MIN NO UNIONS IN LINE SEE SECTION 1211.10 94 UPC MUST SCREW DOWN WATER HEATER FLU VENT TO COLLAR WATER HEATER MUST HAVE ENCLOSURE TO PROTECT IT FROM ELEMENTS (WIND) |