Permit: T00PL02551

Parcel: 122184330


Addresses:

3560 E CODY ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T00PL02551

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/20/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*
03/15/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999* 1) 3/4" GAS LINE IS TOO SMALL OF LINE FOR TOTAL CFH DEMAND. THIS LINE MUST BE 1" UP TO FIRST APPLIANCE FROM METER SEE TABLE 12-3 94 UPC
01/03/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*
MUST HAVE ACCESS TO ALL GAS APPLIANCS INSIDE DWELLING PLEASE CALL 791-5550 TO MAKE A APPOINTMENT.
GAS PRESSURE TEST WAS DOWN TO ZERO LBS MUST HAVE 10 LBS MIN
NO UNIONS IN LINE SEE SECTION 1211.10 94 UPC
MUST SCREW DOWN WATER HEATER FLU VENT TO COLLAR
WATER HEATER MUST HAVE ENCLOSURE TO PROTECT IT FROM ELEMENTS (WIND)