Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T00PL02347
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* CORRECTIONS HAVE BEEN MADE ON WATER HEATER |
|
12/13/2000 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* WATER HEATER NOT READY 514.2 SINGLE WALL JOINTS NOT FASTENED 516.5 CLEARANCE SINGLE WALL 6" COMBUSTIBLE 1" ON DOUBLE WALL MANUFACTORS INSTRUCTIONS COMBUSTION AIR SEC TABLE 5-1 94UPC MIN 100 UP AND DOWN REFIEF SHALL EXTEND FROM THE VALVE TO OUTSIDE OF BLDG OR OTHER APPROVED LOCATIONS FLOOR IS NOT APPROVED LOCATION SEC 608.5 |
|
12/05/2000 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* PLEASE POST ADDRESS AT UNIT NO ADDRESS POSTED AT UNITS |