Permit: T00PL02214

Parcel: 122131170


Addresses:

4114 E FAIRMOUNT ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/29/2000 PLUMBING - FINAL Approved IVRS - Inspection 0000*
GAS PRESSURE TEST OK
GAS SHUT OFF VALVES OK
WATER HEATER FLU VENT, P&T DRAIN OK
ALL CORRECTIONS HAVE BEEN MADE
11/27/2000 PLUMBING - FINAL Denied GAS LINE IS UNDERSIZED FOR CFH DEMAND THIS LINE MUST BE MIN 1" TO THE FIRST APPLIANCE SEE TABLE 12-3 94 UPC
WATER HEATER P&T DRAIN MUST GO TO DAYLIGHT
WATER HEATER FLU VENT MUST BE SCREWED DOWN WITH SHEET METAL SCREENS
GAS LINE FOR DRYER MUST BE MIN 6" ABOVE FLOOR SEE SECTION 1211.3 94 UPC
MUST STRAP DOWN 1/2" DROP FOR WALL FURNACE
RE TEST THE SYSTEM
11/24/2000 PLUMBING - FINAL Denied IVRS - Inspection 0999*
11/21/2000 PLUMBING - FINAL Denied IVRS - Inspection 0999*
I MUST HAVE ACCESS TO ALL GAS APPLIANCES IN APTS
MUST STRAP DOWN 3/4" GAS DROP TO METER ON EAST WALL
MAKE SURE PLDG CONTRACTOR HAS CALCULATED BUT AND CFH DEMAND FOR PROPER PIPE SIZE