Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2000 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* PRESSURE TEST OK ILLEGAL VALVES REMOVED AND RIGHT/LEFT HAND NIPPLE AND COUPLING INSTALLED REAR HEATER VALVE OK OK FOR GAS |
|
| 11/14/2000 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999* NO PRESSURE TEST NEED 10 LBS FOR 15 MINUTES MINIMUM ALL VALVES MUST HAVE AGA OR CSA STAMP IN VALVE BODY AT METER BRANCH TO REAR BLDG JUST INSIDE REAR BLDG LOW AT HEATER IN REAR BLDG JUST INSIDE REAR BLDG LOW AT HEATER ON REAR BLDG |