Permit: T00PL01940

Parcel: 119031940


Addresses:

402 W 41ST ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/07/2000 PLUMBING - FINAL Approved IVRS - Inspection 0000*
11/14/2000 PLUMBING - FINAL Denied IVRS - Inspection 0999$
11/07/2000 PLUMBING - FINAL Denied IVRS - Inspection 0999*
TRUCK IN DRIVEWAY NO ONE ANSWERED THE DOOR
ALL FITTINGS AND MARRED PIPE BELOWGRADE MUST BE WRAPPED
UNIONS MUST BE PRECEDED BY BULDING SHUT OFF VALVE
WATER HEATER NOT RATED FOR OUTDOOR USE MUST PROVIDE ENCLOSURE
MUST PROVIDE PERMIT FOR ADDITONAL PLUMBING INSTALLED IE WASHER BOX AND ABS AND COPPER REPIPE
NOTE: IF YOU ARE CITED FOR WORK WITHOUT PERMIT PERMITS FEES WILL BE DOUBLED