Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2000 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* GAS PRESSURE TEST OK GAS SHUT OFF VALVES OK WATER HEATER FLU VENT, P&T DRAIN OK FURNACE FLU VENT OK OK TO BACKFILL TRENCH |
|
| 10/18/2000 | PLUMBING - GAS PRESSURE TEST | Denied | WATER HEATER MUST HAVE PRESSURE RE LITE VALVE AND DRAIN TO DAYLIGHT GAS LINE CAN NOT HAVE ANY UNION IN LINE MUST REPLACE WITH RIGHT AND LEFT HAND NIPPLES ON ROOF GAS LINE IS UNDERSIZED FROM METER TO HOUSE. GAS LINE FOR CFH DEMAND MUST BE MIN 1" FROM METER TO HOUSE SERVICE FLU VENT FOR WATER HEATER AND FURNACE MUST TERMINATE 1'-10" ABOVE COOLER |