Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T00PL01834
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/16/2000 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* TEST OK TO EXISTING FIXTURES CORRECTIONS HAVE BEEN MADE |
|
10/12/2000 | PLUMBING - FINAL | Not ready for Inspection | PLEASE CORRECT VENT AT WATER HEATER VENT THROU ROOF TEST DOWN AT THIS TIME PLEASE PROVIDE 10 LBS TEST | |
10/11/2000 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* TEST TO REMAIN ON FOR NEXT INSPEPECTION PLEASE SEE VENT ON WATER HEATER PLEASE PROVIDE 1" CLEARANCE ON DOUBLE WALL VENT 1/4" PITCH ON VENT CONNECTOR 6" CLEARENCE ON SINGLE WALL VENTS FROM COMBUSTIBLES. ANCHOR ALL GAS PIPING TO HOLE STRAPS OR BETTER LOOK BEHING HANGS |
|
10/05/2000 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* CALL AGAIN WHEN READY |