Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2000 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* GAS PESSURE TEST OK GAS SHUT OFF VALVES OK WATER HEATER P&T DRAIN FLU VENT OK OK TO BACKFILL TRENCH |
|
| 10/04/2000 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999* 1. MUST PROVIDE AIR PRESSURE TEST 10 LBS MIN 2. MUST USE APPROVED COUPLINGS ON 1" GAS LINE, REMOVE THREAD PROTECTORS 3. MUST USE APPROVED TAPE PRIMER FOR ALL JOINTS UNDERGROUND THEY APPLY TAPE 4. MUST SCREW DOWN WATER HEATER FLU VENT AT ALL JOINTS 3- SCREWS EACH 5. MUST RUN P&T DRAIN FOR WATER HEATER TO DAYLIGHT 6. MUST HAVE AGA APPROVED GAS SHUT OFF VALVE AT FURNACE GAS PACK ON ROOF MUST BLOCK GAS LING ON ROOF |