Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2000 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* GAS PRESSURE TEST OK GAS SHUT OFF VALVES OK WATER HEATER FLU VENT, P&T DRAIN OK FURNACE FLU VENT OK |
|
| 10/06/2000 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* I MUST HAVE ACCESS TO ALL GAS APPLIANCES IN DWELLING |
|
| 09/29/2000 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1. NO ONE HOME. I must have access to all appliance inside as requested 2. gas pressure test was below 10 16 min |
|
| 09/21/2000 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* GAS PRESSURE TEST WAS BELOW 10 LBS MIN GAS LINE MUST BE MIN 12" OF COVER SER SECTION 1211.5 94 UPC AS REQUESTED TWICE |
|
| 09/18/2000 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* GAS PRESSURE TEST WAS BELOW 10 LB MIN NO CORRECTIONS HAVE BEEN MADE AS REQUESTED MUST PAY REINSPECTION FEE BEFORE NEXT INSP |
|
| 09/08/2000 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* SEE SECTION 1211.5 94 UPC MUST HAVE ACCESS TO ALL GAS APPLIANCES INSIDE |