Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/11/2001 | PLUMBING - FINAL | Denied | 1. NEED COMBUSTION SUPPLY AND RELIEF OPENINGS IN DOOR OF WATER HEATER ENCLOSURE. 2. EXTEND T.P.R.V. DISCHARGE LINE DOWN TO BETWEEN 6" AND 24" ABOVE FLOOR LEVEL. CANNOT BE THREADED ON DISCHARGE END. 3. NEED PERMIT FOR SEWER/WASTE PIPING. 4. NEED APPROVED DRAWING FOR GAS PIPE SIZING. | |
| 08/29/2000 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* | |
| 08/22/2000 | PLUMBING - FINAL | Denied | NO ENCLOSURE FOR WATER HEATER WATER HEATER FLUE PIPING NOT CONNECTED BLACK IRON PIPE NOT ACCEPTABLE MATERIAL FOR WATER T&P DOES NOT EXTEND TO WITHIN 6" AFF WATER HEATER NOT SET ON CONCRETE PAD I NEED TO SEE A DRAWING WITH THE GAS SIZING TO EACH APPLIANCE PER 94 UPC THERE ARE SEVERAL PLUMBING ISSUES THAT NEED TO BE ADDRESSED INCLUDING VENT PIPE FULL OF HOLES ABS WASTE PIPING DUMPING ONTO BACK PROCH THIS LIST MAY NOT INCLUDE ALL CODE VIOLATIONS AND CONTRACTOR IS RESPONSIBLE FOR PERMITS TO CORRECT UNSAFE OR UNACCEPTABLE CONDITIONS |