Permit: T00PL01550

Parcel: 133360370


Addresses:

525 N BANFF AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/14/2000 PLUMBING - FINAL Approved
09/12/2000 PLUMBING - FINAL Denied IVRS - Inspection 0999*
GAS PRESSURE TEST WAS BELOW 10 LBS MIN
09/05/2000 PLUMBING - FINAL Denied IVRS - Inspection 0999*
GAS PIPING UNDERGROUND MUST HAVE AT LEAST 12" OF COVER SEE SECTION 1211.5 94 UPC
WER DO NOT ACCEPT AGA STAMP ON HANDLE OF SHUT OFF VALVE MUST BE STAMPED ON BODY OF VALVE
WATER HEATER FLEX LINE FOR P&T DRAIN MUST BE MIN 12" AND P&T DRAIN MUST TERMINATE 3" A.F.F. SEE SECTION 608.5 C OF T MODIFICATIONS
08/21/2000 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*