Permit: T00PL01288

Parcel: 110081780


Addresses:

4441 E BERMUDA ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/24/2000 PLUMBING - GAS PRESSURE TEST Approved
07/21/2000 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*
1. MUST REMOVE UNIONS ON ROOF AND REPLACE WITH RIGHT AND LEFT HAND NIPPLES
2. MUST USE APPROVED TWO HOLE STRAPS ON GAS LINE
07/20/2000 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*
1. GAS PIPE ON SIDE OF HOUSE NEEDS TO BE ANCHORED TO THE WALL
2. GAS PIPE ON ROOF IS NOT BLOCKED OR STRAPPED PROPERLY
3. ALL UNIONS IN GAS LINES MUST HAVE A SHUT OFF VALVE BEFORE THE UNION
4. NEED TO ACCESS INSIDE THE HOUSE TO SEE APPROVED GAS SHUT OFF VALVES AT EACH APPLIANCE
07/19/2000 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*
1. MUST PROVIDE AIR PRESSURE TEST ON ENTIRE SYSTEM 10 LBS MIN