Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T00PL01269
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/21/2000 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | THIS IS 4TH INSPECTION PROVIDE PLUMBING CONTRACTOR | |
07/17/2000 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | 1. LEAK AT PVC VALVE PLEASE PROVIDE LISTING ON VALVE 2. TRANSISSION FROM PVC COPPER OR MAKE IRON PIPE SEE SEC 606.2.2 FEMALE PVC SCREWED FITTING FOR WATER PIPING ARE PROHIBITED USE MALE ADP ON PVC SIDE |
|
07/14/2000 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | OK TO COVER FORM METER BOY TO FENCE. COULD NOT ENTER REAR YARD PVC VLAVE NOT TO CODE/NOT A LISTED VALVE PROVIDE LISTED VALVES ALSO ALL HOSE BIBD REQUIRE A VACUMN BREAKER |