Permit: T00PL01163

Parcel: 10320084B

Inspection Status: Partial Approval

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
11/16/2000 PLUMBING - SEWER HCS CONNECT Partial Approval
11/03/2000 PLUMBING - SEWER HCS CONNECT Partial Approval TEST OK FROM M-H #3TO M-H #4
FROM M-H #3 TO M-H #2
FROM M-H#2 TO M-H #8
FROM M-H#2 TO M-H #1
PLEASE PROVIDE VARIFICATION OF GRADE BY FINAL
10/27/2000 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection 0000*
10/26/2000 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection 0000*
10/24/2000 PLUMBING - SEWER HCS CONNECT Partial Approval RUN FROM M-H #8 OK S.W. M-H #4. TOTAL RUN AND CO OK
WILL TEST AT LATER DATE
10/23/2000 PLUMBING - SEWER HCS CONNECT Partial Approval FROM M-H #8 APROX 80' TO CO OK ALSO 27'0 FROM M-H #8
10/19/2000 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection 0000*
10/18/2000 PLUMBING - SEWER HCS CONNECT Partial Approval M-H #2-TO M-H #3OK
M-H #3 TO M-H #4 OK ALSO 100'
WEST OF M-H #4 OK TO BACKFILL
WILL TEST AT LATER DATE
10/17/2000 PLUMBING - SEWER HCS CONNECT Partial Approval FROM M-H #1 8" SDR 35 TO M-H #2 OK TO BACKFILL
WILL NEED VARIFICATION OF GRADE OF COMPLETE SEWER BY FINAL.
OK TO BACKFILL WILL NEED TEST AT LATER DATE. ALSO APROX 100' 8" SDR NORTH OF M-H #2