Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/05/2000 | PLUMBING - FINAL | Denied | IVRS - Inspection 0000* | |
| 07/03/2000 | PLUMBING - FINAL | Denied | 1. WATER HTR HAS TRAP IN P&T DRAIN MUST PROVIDE DRAIN IN LINE AT LOWEST POINT. 2. MUST HAVE 1" CLEARANCE AROUND DOUBLE WALL FLU VENTS FOR FURNACE AND WATER HEATER 3. 3/4" GAS LINE IS TO SMALL FOR BTU AND CFH DEMAND. MUST BE 1" UP TO TEE AT WATER HEATER AND FURNACE ROOM TO DRYER ROOM 4. 3/4" GAS LINE UNDERGROUND HAS THREAD PROTECTOR. THIS COUPLING IS NOT APPROVED MATERIAL |