Permit: T00PL01106

Parcel: 11454001A

Inspection Status: Correction Required

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T00PL01106

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/20/2000 PLUMBING - YARD WTR LINE/TEST Correction Required ADDTL COMMS - 1. WATER HTR WILL REQUIRE A EXPANSION TANK TO PREVENT THERMAL EXPANSION DUE TO CLOSE SYSTEM BY BACKFLOW PERVENTER 2. NOTE: HOSE BIBS REQUIRE VACUMN BREAKERS
06/20/2000 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0000*
06/13/2000 PLUMBING - YARD WTR LINE/TEST Correction Required ADDTL COMMS - 1. NO EXPOSED PVC ALLOWED 2. CAN NOT SCREW COPPER INTO PVC 90 DEGREE 3. OK TO BACKFILL TRENCH 4. WHAT IS BACKFLOW PREVENTER SERVING?
06/13/2000 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection 0000*